ACR Journal

December 2021 | January 2022 DESIGN IN DETAIL – SPONSORED BY COOL DESIGNS LIMITED 34 Volume 8 No.1 Seamless 0-10v control on DX to AHU Overview Electrically driven options for AHU heating and cooling are being considered more and more, due to the legislation change and direction towards net zero carbon. Utilising Direct Expansion (DX) on AHU Coils allows for a simple, e cient, and cost-e ective heating and cooling method. Heat pump (based on Toshiba) Heat Pumps use the AHU coils part of `their own` refrigeration circuit, delivering either hot gas when the AHU DX coil becomes the `condenser` during heating requirement, or, when the cycle is reversed, delivering cool suction gas when the AHU DX coil becomes the evaporator (or cooler). It`s all about control. The air-cooled heat pump contains the refrigerant `pump`. It also contains one of the heat-exchanger coils. This coil is the condenser whilst cooling & the evaporator whilst heating. The unit has a reversing valve (heat or cool). So, by utilising the heat exchanger (DX) coil in the AHU we have our main refrigeration circuit components. Controlling the air The compressor has inverter drive. Inverter is controllable. Until recently the supply duct temperature was di cult to control as, the available system controls at the time, relied on return air/room air and adjusted to suit. With the advent of the FDP3 `Gismo from the Gods` the inverter compressor (and therefore quantity of heating or cooling) can be controlled from a 0-10v signal. The RBC AHU1 Control Box is mounted at the AHU Coil and contains all necessary boards etc for the operation of the refrigeration circuit. The FDP3 0-10v `gismo` sits within the panel. It can also be supplied loose for fitting in the BMS panel or other. One RBC AHU1 Control box and One FDP3 is needed per refrigerant circuit. Multiple circuits To achieve the heating and cooling duty, and to have an element of resilience, more than one refrigerant circuit is often installed. The first example below shows 2 no heat pump serving a single AHU Coil. Note the 2 no RBC control boxes mounted on the AHU, at the coil. They need to be in close proximity as sensors lead from this control box to the DX coil itself, ensuring correct operation. The second example below shows 5 no `twin fan` heat pumps serving a single AHU coil for a hospital project. The two smaller units on the right are serving cassette split systems. Duty & number of circuits The heat pumps are from the Digital and Super Digital range of Heat Pumps from Toshiba. Nominal duty per unit ranges from 5kW to 25kW approx. The second example above, with the 5 no units had a DX coil requirement of 120kW. 5no units were supplied, with 5no RBC AHU1 control box each with an FDP3 `gismo` within. Efficiency • Cooling EER between 2.7 and 3.7 over the range. • Heating COP between 3.4 and 4.1 over the range Summary E cient operation and simplistic approach allow for many applications of AHU DX using heat pumps. Seamless 0-10v inverter control on a wide range of heating and cooling loads, at AHU Coils, can be achieved using multi refrigerant circuits. Toshiba `Inverter` Twin Rotary Compressor Toshiba `Inverter`TwinRotaryCompressor Andy Bradison Toshiba 'Inverter' Twin Rotary Compressor

RkJQdWJsaXNoZXIy Mzg1Mw==